3512.4.2. Horizontal Airflow Direction Control12.5. Quiet operation (Cooling Mode/Cooling area of Dry Mode)A. PurposeTo provide quiet cooling operation compare to normal operation.B. Control conditiona. Quiet operation start condition• When “quiet” button at remote control is pressed.Quiet LED illuminates.b. Quiet operation stop condition1. When one of the following conditions is satisfied, quiet operation stops:a. Powerful button is pressed.b. Stop by OFF/ON switch.c. Timer “off” activates.d. Quiet button is pressed again.2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.5. During quiet operation, if timer “on” activates, quiet operation maintains.6. After off, when on back, quiet operation is not memorised.OperationModeHorizontal Automatic Operation Operation for 5 min. after Powerful-ON orthe Neural Control is stabilized.Cooling• The louver horizontally swings at a fixedcycle.Horizontal Automatic Operation Operation for 5 min. after Powerful-ONDry• The louver horizontally swings at a fixedcycle.• The louver horizontally swings at a fixedcycle.Horizontal Automatic Operation Operation after Powerful-ONHeating When heat exchangertemperature is below 32°C.When heat exchanger is between32°C (, incl.) and 56°C (, excl.)When the Neural Control is stabilized.• The louver horizontally swings at a fixedcycle.When the Neural Control is not stabilized.In Quick Warm OperationIn Warm Heating OperationWhen heat exchangertemperature is 56°C or more.