10.5. Auto Restart Control· if there is a power failure, operation will automatically be restarted when the power is resumed. It will start with the previousoperation mode and airflow direction. (Time Delay Safety Control is valid)1. Control start conditions<1> The 24-hour timer must not be set.<2> The sleep timer must not be set.Auto restart control is not available when timer or sleep mode is set.2. Description of control<1> In the case of manual operation, the operation mode, temperature setting, fan speed and airflow direction before the poweris turned off are restored.<2> In the case of automatic operation, after the power is restored operation starts with the determination of the mode.<3> While the air conditioner odour clear timer has been set, the setting is cancelled, and operation is transferred to the modebefore the power is turned off.<4> While the air conditioner odour clear operation (with timer / without timer setting) are being performed, both of theseoperations are completed, and operation is transferred to the operation mode prior to these operations.Example: When the power is turned off during an outdoor unit cooling operation23CS-ME7EB1E / CS-ME10EB1E / CS-ME12EB1E / CS-ME14EB1E