8.5. SOFT DRY OPERATION8.5.1. Room Temperature ControlAt the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal settingtemperature, then the operation will shift to Soft Dry with indoor fan speed SLo.Refer to8.3.1. Compressor Operation Frequency· Thermostat OFF temperature = Thermostat ON temperature.· The Comp. Operation Frequency Command can be changed every 30 seconds.· 30 minutes from the start of the operation, the compressor is operating at Fc max.· The Thermostat OFF when the intake air temperature reaches 1°C below internal setting temperature and continues for 3minutes.· When the Thermostat of both Indoor Units OFF, the Compressor stops.· When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)· When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.· When the compressor stops, the outdoor fan motor stops 30 seconds later.8.5.2. Deodorizing Control· This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available during anti-freezingcontrol.· When the Thermostat ON operation, the deodorizing status starts from 1 → 2 → 3.· When the Thermostat OFF operation, the deodorizing status starts from 4 → 5 → 6 → 7.· If the Thermostat OFF operation after 3 minutes, the deodorizing status will start from 6.8.5.3. Sensible Heat Control· This control is to improve the feeling in high fan speed during low Comp. Operation Frequency Command Number. When theComp. Operation Frequency Command Number is less than 4, the fan speed will reduce. When the Comp. OperationFrequency Command Number is above 5 continuously for 5 minutes, the fan speed will resume to normal condition.20CS-MVG103KE / CU-MVG153KE