3312.1.8. Outdoor Fan Motor OperationOutdoor fan motor is operated with 15 fan speed number of rotations. It starts when compressor starts operation and it stops 30seconds after compressor stops operation.12.1.9. Airflow Direction1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchangertemperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).12.1.9.1. Vertical Airflow1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as statedabove. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1below. When the air conditioner is stopped using remote control, the vane will shift to close position.2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positionsof the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to closeposition.Operation Mode Airflow Direction Vane Angle (°)1 2 3 4 5Heating Auto with Heat ExchangerTemperatureA Upward fix 27B Downward fix 70C Upward fix 27D Downward fix 27Manual 27 39 49 60 70Cooling and Ion Auto (Anti-Dew Control) 27 ~ 49 (30 ~ 39)Manual (Anti-Dew Control) 27 (30) 34 (32) 39 (35) 44 (37) 49 (39)Soft Dry Auto (Anti-Dew Control) 27 ~ 49 (30 ~ 39)Manual (Anti-Dew Control) 27 (30) 34 (32) 39 (35) 44 (37) 49 (39)