2812.5. Indoor Fan Speed Control• Indoor Fan Speed can be set using remote control.12.5.1. Fan Speed Rotation Chart12.5.2. Automatic Fan Speed Control• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.- Fan speed rotates in the range of Hi, Me and Lo-.- Deodorizing Control will be activated.• Auto Fan Speed during cooling operation:1. Indoor fan will rotate alternately between off and on as shown in below diagram.2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from thestart of compressor. This cause the room temperature to achieve the setting temperature quickly.4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerantin liquid from returning to the compressor.5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in theroom. This is to obtain the actual reading of the intake air temperature.6. When the compressor resume operation, indoor fan will operate at Me fan speed (after 70 seconds from the restart ofcompressor) to provide comfort and lesser noise environment.Speed CS-PW18GKXCool, Dry HeatS Hi Hi 1490Hi 1470Me Me 1370Lo+ Lo 1270Lo 1190Lo- Lo- 980S Lo S Lo 760SS Lo 300Q SHi Q Hi —Q Hi —Q Me Q Me —Q Lo —Q Lo —