37[Heating]• According to indoor pipe temperature, automatic heating fan speed is determined as follows.B. Feedback control• Immediately after the fan motor started, feedback control is performed once every second.• During fan motor on, if fan motor feedback 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error counterincrease, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan motor error is detected.Operation stops and cannot on back.12.1.7. Outdoor Fan Motor OperationOutdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds aftercompressor stops operation.12.2. Airflow Direction1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchangertemperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).12.2.1. Vertical AirflowOperation Mode Airflow Direction Vane Angle ()1 2 3 4 5Heating Auto with Heat Exchanger A 20B 45Temperature C 32Manual 20 32 45 57 68Cooling and e-ion Auto 20 ~ 45Manual 20 26 32 37 45Soft Dry Auto 20 ~ 45Manual 20 26 32 37 45