5612.10 Auto Restart Control1 When the power supply is cut off during the operation of air conditioner, the compressor will re-operate withinthree to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to beselected randomly) after power supply resumes.2 This type of control is not applicable during ON/OFF Timer setting.3 This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.12.11 Indication PanelLED POWER TIMER QUIET/ECONOMY POWERFULColor Green Orange Orange OrangeLight ON Operation ON Timer Setting ON Quiet/Economy Mode ON Powerful Mode ONLight OFF Operation OFF Timer Setting OFF Quiet/Economy Mode OFF Powerful Mode OFFNote: If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operationmode judgment, or ON timer sampling. If Timer LED is blinking, there is an abnormality operation occurs.12.12 HA Terminal (HAJEM-A) Enable digital connection from indoor unit to external devices. Control items:1 Start/stop input.2 Start/stop signal output. Condition1 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.(1 pulse signal: shortage status 200 ~ 300 msec)2 3-4 (Static output): 5V output during the unit ON. No output at OFF.