35o Active e-ion Air Purifying system breakdown error: Judgment Method• When hi-feedback voltage (at microcontroller) supplied to filter during e-ion stop, Active e-ion AirPurifying system breakdown error shows immediately.• It is due to indoor PCB or filter’s high voltage power supply damage.• Operations except e-ion continue. Both Timer indicator and e-ion indicator blink. Troubleshooting Method• Press “e-ion” button or “OFF/ON” button to stop the operation.• Change main circuit board or filter’s high voltage power supply.• When lo-feedback voltage supplied to Active e-ion Air Purifying system during e-ion operation, e-ionindicator and Timer indicator stop blinking.11.12 Mild Dry Cooling Operation• This operation helps to prevent decreases in room humidity while maintaining the setting temperature.• During unit running at Cooling operation mode, if “Mild Dry Cooling” button is pressed, Mild Dry Cooling operationstarts and Mild Dry Cooling indicators turns ON.• Mild dry cooling operation is unavailable when the unit is operating Auto mode, Soft Dry mode, Patrol individualoperation or e-ion individual operation.• Mild dry cooling operation is cancelled when the unit turned OFF, or when the operation mode changed fromCooling to other mode.• Powerful, Quiet and Mild Dry Cooling mode cannot function at the same time, the unit will follows the operationaccording to the last signal received.• During this operation, the compressor frequency changes according to operating condition to prevent roomhumidity decreases and when AUTO AIR SWING is set, the vertical airflow direction fixed at lower limit position.