6414 Troubleshooting Guide14.1 Refrigeration Cycle SystemIn order to diagnose malfunctions, ensure the air conditioner is freefrom electrical problems before inspecting the refrigeration cycle.Such problems include insufficient insulation, problem with thepower source, malfunction of a compressor and a fan. The normaloutlet air temperature and pressure of the refrigeration cycledepends on various conditions, the standard values for them areshown in the table to the right.Normal Pressure and Outlet Air Temperature (Standard)Gas PressureMpa(kg/cm 2G)Outlet airTemperature(°C)Cooling Mode 0.9 ~ 1.2 (9 ~ 12) 12 ~ 16Condition: Indoor fan speed = HighOutdoor temperature = 35°C at cooling mode.Compressor operate at rated frequencyDifferent in the intakeand outletair temperatures NormalValue of electric currentduring operationDusty condenserpreventing heat radiationExcessive amountof refrigerantGas sidepressure Inefficient compressorInsufficient refrigerantClogged strainer orcapillary cube• Measuring the airtemperature different• Measuring electric currentduring operation• Measuring gas sidepressureMore than 8̓ C(15 minutes after anoperation is started) atcooling mode.Less than 8̓ C at the cooling modeHigher than specifiedCoolingMode HighLowLowLower than specified