Cooling in operation according to Remote Control setting.Time Delay Safety Control (3 minutes)7 minutes Time Saved ControlAnti-Freezing Control• If the temperature of the indoor heat exchanger fallscontinuously below 1°C for 4 minutes, the compressor turnsoff to protect the indoor heat exchanger from freezing. Thefan speed setting remains the same.• Compressor recommences when the indoor heatexchanger temperature rises to 10°C (Recovery).3 minutes waiting of Time Delay Safety Control isvalid for Cooling Operation.8 Operation Details8.1. Cooling Mode Operation• When the compressor is stopped by Power Switch, Remote Control or there is a power failure, it restarts after 3 minutes whenthe Power Switch, Remote Control is turned ON or the power supply is resumed.• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is below the compressorON temperature.12CS-V28BKP5/CU-V28BKP5