2910. Installation Instruction10.1 Select The Best Location If an awning is built over the unit to prevent directsunlight or rain, be careful that heat radiation fromthe condenser is not obstructed. There should not be any animal or plant whichcould be affected by hot air discharged. Keep the spaces indicated by arrows from wall,ceiling, fence or other obstacles. Do not place any obstacles which may cause ashort circuit of the discharged air.Refrigerant piping sizeOutdoor Unit CU-4E27*** CU-5E34***Liquid - side ø 6.35 t0.8 ø 6.35 t0.8Gas - side ø 9.52 t0.8*(ø 12.7 t0.8)ø 9.52 t0.8*(ø 12.7 t0.8)*In case of indoor is CS-E21***, CS-XE21***,CS-ME21***, CS-E24***, then ø 12.7 t0.8 gas-pipe size must be used together with CZ-MA2P(pipe size expander)Outdoor Unit CU-4E27*** CU-5E34***Equivalent length 45 m 45 m If total piping length of all indoor units exceed theequivalent length listed above, additional chargewith 20g of refrigerant (R410A) for each additionalmeter of piping.Allowable piping lengthOutdoor Unit CU-4E27*** CU-5E34***Allowable piping length of each indoor unit (min. ~ max.) 3 m ~ 25 m 3 m ~ 25 mAllowable total piping length of all indoor unit 70 m or less 80 m or lessHeight difference between indoor and outdoor unitOutdoor unit located on upper side 15 m or less 15 m or lessOutdoor unit located otherwise 7.5 m or less 7.5 m or lessHeight difference between indoor unitOutdoor unit located on upper side 7.5 m or less 7.5 m or lessOutdoor unit located otherwise 15 m or less 15 m or lessAMP Air Conditioningwww.ampair.co.uk | sales@ampair.co.uk