10 How to Install10.1. Before installing the air conditioner, please read the following:10.1.1. Electrical Work.• Always use at the rated voltage and with a specific air conditioning circuit.• Power supply point shall be the place where there is ease for the power disconnection in case of emergency.• Some installation locations may require installation of a short-circuit breaker.• Time delay fuse or circuit breaker rating is 16 Ampere for CW-C172KR/CW-A172KR/CW-C202KR/CW-A202KR.• Nominal cross sectional area of power supply wire must be 3 core x 2.5 mm2 or above.• The power supply must be from an independent circuit.• All electrical installations must be made in accordance with local wiring and safety regulations wherever applicable.• There must be a double pole switch with minimum of 3 mm contact gap in the fixed installation circuit.10.1.2. Select the Best Location.• Install the unit at the nearest power outlet.• The air conditioner should be installed in a dry place where there are no draughts.• Condensation from the air conditioner must be drained into an appropriate location.• Do not install in a location where flammable gas leaks is a possibility.• Usage in locations where the air is salty such as coastal areas or near hot spas, or where sulphurous gas is generated, maylead to a malfunction.• Do not install this appliance in a laundry room or other locations where water may drip from the ceiling, etc.• Select an installation location which is rigid and strong enough to support or hold the unit and select a location for easymaintenance.10.2. Preparation for Installation.• There should not be any obstacles surrounding the unit.• Prepare an installation hole that is only slightly bigger than the cabinet size.15CW-C172KR / CW-C202KR / CW-A172KR