FP0 PROFIBUS DP Slave or Remote I/O UnitFor cost effective control of distributed field deviceThe FP0 DPS2 can operate either as a DP slave module or as a remote I/Osystem to which different decentralised inputs and outputs can beconnected. A DIP switch can be used to switch between the two modes:Mode 1:DP-Slave module. Connect the FP0 or FP∑ (Sigma) CPU + expansionmodules to the PROFIBUS network.Mode 2:Remote I/O. Connect up to three expansion modules without CPU to thePROFIBUS network.In Remote I/O mode the unit can be connected to any PLC which offers aPROFIBUS communication interface, making it totally independent ofNAiS PLCs.Item DescriptionType designationPROFIBUS standards complied withFP0 DP Slave unit, Ord. No. FP0DPS2EN 50170, DIN 19245 Part 1 and Part 3Baud rates 9.6 / 19.2 / 93.75 / 187.5 / 500 / 1,500 / 3,000 / 6,000 / 12,000 Kbaudautomatic baud rate detectionRange of adresses that can be set 0..125PROFIBUS connectionConfiguration9-pin D-sub connector2 words input / 2 words output, up to 6 words input / 6 words output if no other expansion is connectedRemote I/O, max. 3 FP0 expansion unitsFP0 communication Via FP0 system busPower supply 24VDC (21.6VDC … 26.4VDC)Max. power consumption 100mAFP0-DPS SpecificationsDP-SlaveRemote I/OPLC(Master)PLC(Slave)Remote I/O(Slave)FP0 DP Slave FP∑ (Sigma) DP SlaveDP Slave Remote I/OConfiguration with digital I/Oup to 96 transistor I/O or up to48 relay I/O are possibleDP Slave Remote I/O Configurationwith analogue I/O up to 12 outputs or24 analogue inputs or up to 24thermocouple inputs are possibleAFP86910FP2 DP or FMS MasterSpecial developed software tools ensureeasy configuration and start-up ofPROFIBUS products.CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net