9 Specifications9.1 Specifications- General specificationsItem SpecificationsConsumption current increasedfor the Control Unit 25mA Max. (24V DC)Operating ambient temperature 0℃ to +55℃Storage ambient temperature -20℃ to +70℃Operating ambient humidity 30%RH to 85%RH (at25°C no condensing)Storage ambient humidity 30%RH to 85%RH (at25°C no condensing)Withstand voltagebetween “all the thermocouple input terminals” and “all the Controlunit power/functional earth terminals”: 500V AC for 1min.between thermocouple input terminal channels: 200V AC for 1 min.Insulation resistancebetween “all the thermocouple input terminals” and “all the Controlunit power/functional earth terminals”: more than 100MΩ(Testing voltage: 500V DC)Vibration resistance 10Hz to 55Hz 1 sweep/min. with double amplitude in 0.75mmfor 10 min. on 3 axes (toward X, Y and Z directions)Shock resistance 98m/s2 for 4 times on 3 axes (toward X, Y and Z directions)Noise immunity 1000V [P-P] Pulse width 50ns, 1μs (using noise simulator)Operating condition Must be free from corrosive gases and excessive dust.Weight about 85g (FP0-TC4)about 95g (FP0-TC8)14