6.1.3 Moving Average Overview of functions• Analog input data sampled by the unit is averaged and stored as digital values.• If moving average is set, analog input data items acquired will be stored in unit memory(UM) as digital values when the number of analog input data items reaches the set numberof moving average times.• When the set number of moving average times is 3 to 64, the maximum and minimumvalues are cut from the data for n times, and the data for (n-2) times is averaged.• When the set number of moving average times is 1 or 2, the latest measured data is storedwithout averaging processing.• When data sampling for the set number of times has not been completed, data is notupdated. When all data are acquired, the data will be updated.• Obtain output (moving average value) to be processed from the following input.Input The number of average times, analog input data for the number of average times, the latet analoginput data, and old analog input dataOutput Moving average value Processing during moving averageAveraging setting example: The number of averaging times is set to 15.Analog signalabc d e f gh ij k lmno p qrAnalog inputprocessingAnalog inputdataAverage of a to o (Max. and min. values are cut.)Average of b to p (Max. and min. values are cut.)Average of c to q (Max. and min. values are cut.)・・・・・・・・・ ConfigurationName Default Setting range and descriptionFunctionsettingAverageprocessing Not execute Select "moving average".Averaging constant K8 Number: 3 to 64 [times] (specified with an unsignedinteger)Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com