166.2 Sub setting modeTo go to the Sub setting mode, press the key while holding down the key in the PV/SV display mode.Set each setting item with the or key, and register the value with the key.Display Item, Function, Setting range Default valueAT (Auto-tuning) selection AT Cancel• Selects auto-tuning Perform/Cancel.Not available for program control standby status and forcontrol actions other than PID action.• : AT Cancel : AT PerformOUT1 (Heating) proportional band setting 2.5%• Sets the proportional band for OUT1 (Heating side).• ON/OFF action when set to 0.0.• Setting range: 0.0 to 110.0% [Percentage of the scaling span(scaling high limit-scaling low limit)]OUT2 (Cooling) proportional band setting 1.0 times• Sets the proportional band for OUT2 (cooling side).• ON/OFF action when set to 0.0.• Not available if Heating/Cooling control option is not added orif OUT1 (Heating side) is ON/OFF action• Setting range: 0.0 to 10.0 times OUT1 (Heating) proportional bandOUT1 (Heating) integral time setting 200 seconds• Sets the integral time.• Setting the value to 0 disables the function. (PD action)• Not available if OUT1 (Heating) is ON/OFF action• Setting range: 0 to 1000 secondsOUT1 (Heating) derivative time setting 50 seconds• Sets the derivative time.• Setting the value to 0 disables the function. (PI action)• Not available if OUT1 (Heating) is ON/OFF action• Setting range: 0 to 300 secondsARW setting 50%• Sets the ARW (anti-reset windup).• Available only for PID action.• Setting range: 0 to 100%OUT1 (Heating) proportional cycle setting• Sets OUT1 (Heating) proportional cycle.• Sets the proportional cycle.• Not available for DC current output type orif OUT1 (Heating) is ON/OFF action.Relay contact: 30secNon-contactvoltage: 3secDC current: Notavailable• Setting range: 1 to 120 secondsOUT2 (Cooling) proportional cycle setting 30 seconds• Sets OUT2 (Cooling) proportional cycle.• Not available if Heating/Cooling control option is not added orif cooling output is ON/OFF action.• Setting range: 1 to 120 secondsManual reset setting 0.0• Sets reset value manually.• Available only for P or PD action.• Proportional band converted value (For DC input, theplacement of the decimal point follows the selection.)A1 value setting 0• Sets A1 action point. Setting the value to 0 or 0.0 disables thefunction (except process high alarm and process low alarm).• Not available if No alarm action, Timer function or Pattern endoutput is selected during A1 type selection• Setting range: See (Table 6.2-1).A2 value setting 0• Sets A2 action point. Setting the value to 0 or 0.0 disables thefunction (except process high alarm and process low alarm).• Not available if No alarm action, Timer function or Pattern endoutput is selected during A2 type selection• Setting range: See (Table 6.2-1).