3WAY VRF SYSTEMRemote Controller Functions4 - 151234567892. Detailed Settings FunctionItem code Item Setting dataNo. DescriptionFan tap setting(Fan tap change in orderto prevent drop in airdischarge caused byfilter installation)DC fan tap operatingmode Purpose0000 Standard Standard (setting at shipment)0001High ceiling use High ceiling setting 1 (with standard panel)For lowstatic-pressure filterUltra long-life filter, oil guard panel, ammonia deodorizingfilter, optical regenerative deodorizing filter0003High ceiling use High ceiling setting 2 (with standard panel)For lowstatic-pressure filter(Antibacterial) high-performance filter (90%)(Antibacterial) high-performance filter (65%)Air-cleaning unit, air-cleaning unit + optical regenerativedeodorizing filter, deodorant (activated charcoal) filterFor air-blockingmaterial For 3-way discharge, when discharge duct is connected0006 For air-blockingmaterial For 2-way dischargeHumidifier ON time(ON time per 60seconds)0000 No humidifier output0001 1 second0002 2 seconds0058 58 seconds0059 59 seconds0060 Continuously ONTimer function changeprohibit0000 Function disabled0001 Function enabledSmudging control 0000 No smudging controlSetting the FlapSeparately*Only for 4-WayCassette type0000000100020003000400050006Setting the FlapSeparately*Only for 4-WayCassette typeSetting the FlapSeparately*Only for 4-WayCassette typeSetting the FlapSeparately*Only for 4-WayCassette type=91=90Flap 1(Motor No. 4)(Motor No. 1)(Motor No. 2) (Motor No. 3)Flap 3Flap 2 Flap 4=92=93ElectricalcomponentboxFlap position12345Flap position during operationSetting dataMove to position 1 and stayWithout separate settingSwingMove to position 2 and stayMove to position 3 and stayMove to position 4 and stayMove to position 5 and stayWhen the flap position is set to4 or 5 and the unit is in thecooling or dry mode, the flapposition is moved to 3 and theoperation is started.The flap swings during theoperation under "Setting theFlap Separately".At this time, the unselected flapsare moved to the position 1 .NOTEAir dischargeportFlap(adjustment forup-downairflow direction)