1536 Reset overload protectorOverload Protector a serves the safety purpose to prevent the water over heating. When the OverloadProtector a trip at high water temperature, take below steps to reset it.a. Take out the cover.b. Use a test pen to push the centre button gently in order to reset the Overload Protector.c. Fix the cover to the original fixing condition.Use test pen to pushthis button for resetOverload protector.15.1 Maintenance for Water Filter Set15.1.1 Service and maintenanceWhen connect CN-CNT connector with computerPlease use optional USB cable to connect with CN-CNTconnector.After connected, it requests for driver. If PC is under WindowsVista or later version, it automatically installs the driver underinternet environment.If PC uses Windows XP or earlier version and there is no internetaccess, please get FTDI Ltd's USB - RS232C conversion ICdriver (VCP driver) and install.http://www.ftdichip.com/Drivers/VCP.htmIf forget Password and cannot operate remote controllerPress for 5 sec.Password unlock screen appears, press Confirm and it shallreset.Password will become 0000. Please reset it again.(CAUTION) Only display when it is locked by password.15.1.2 Maintenance menuSetting method of Maintenance menuMaintenance menu 17:26, WedActuator checkTest modeSensor setupReset passwordSelect ConfirmPress for 5 sec.Items that can be set Actuator check (Manual ON/OFF all functional parts)(CAUTION) As there is no protection action, please becareful not to cause any error when operatingeach part (do not turn on pump when there is nowater etc.) Test mode (Test run)Normally it is not used. Sensor setup (offset gap of detected temp of each sensorwithin -2~2°C range)(CAUTION) Please use only when sensor is deviated.It affects temperature control. Reset password (Reset password)