IntroductionUse of the devices in the industrial area (limit values class C3 in accordancewith EN 61800-3)The following mains filters are available for independent utilization:Device: PSU Limit valueclassReference: Axis systemwith motor cableMains filterOrder No.:P10 C3 < 6 x 10 m NFI03/01P10 C3 < 6 x 50 m NFI03/02P20 C3 < 6 x 50 m NFI03/03P30 C3 < 6 x 50 m NFI03/03Connection length: Connection between mains filter and device:unshielded: < 0.5 mshielded < 5 (fully shielded on ground - e.g. ground of control cabinet)2.7.1.2 Conditions of utilization for cables / motor filterMotor and Feedbackcable:Operation of the devices only with motor and feedback cables whose plugscontain a special full surface area screening.<80m per axis (the cable must not be rolled up!)The entire length of the motor cable per axis combination may not exceed 300m.A motor output filter is required for motor cables >20 m: ECM-0001-04 (max. 6.3 A nominal motor current) ECM-0001-01 (max. 16 A nominal motor current)ECM-000 1-02 (max. 30 A nominal motor current)Shielding connection ofthe motor cableThe cable must be fully-screened and connected to the device housing. Use thecable clamps/shield connecting terminals furnished with the device.The shield of the cable must also be connected with the motor housing. The fixing(via plug or screw in the terminal box) depends on the motor type.< 80mCorresponding to the specifications of the terminal clamp with a temperature rangeof up to 60°C.Cable installation: Signal lines and power lines should be installed as far apart as possible. Signal lines should never pass close to excessive sources of interference(motors, transformers, contactors etc.). Do not place mains filter output cable parallel to the load cable.2.7.1.3 Additional conditions of utilizationMotors: Operation with standard motors.Control: Use only with aligned controller (to avoid control loop oscillation).Grounding: Connect the filter housing and the device to the cabinet frame, making sure thatthe contact area is adequate and that the connection has low resistance and lowinductance.Never mount the filter housing and the device on paint-coated surfaces!Accessories: Make sure to use only the accessories recommended by Parker.Connect all cable shields at both ends, ensuring large contact areas!This is restricted operation category product according to EN 61800-3. This productcan cause high-frequency disturbance in domestic areas. Users are asked to takesuitable action if this proves to be the case.Compax3M motorcableCompax3M encodercable:Cable10 192-120148N13 2019-06Multi-axis devices