QUANTECH72SECTION 5 - TECHNICAL DATAFORM QTC4-NM1ISSUE DATE: 4/2/2018ALL DIMENSIONS - INCHES (MM)QTC4A B C DENOZZLESIZEWATERVOLUMEGALLONS(LITERS)MINIMUMCHILLEDWATER FLOWRATEGPM (L/S)MAXIMUMCHILLEDWATERFLOW RATEGPM (L/S)MODELCOND.150 S 15.1(384)26.5(673)6.8(173)34.5(876) 5 58(220) 170 (11) 650 (41)165 H 15.1(384)26.5(673)29.2(742)56.1(1425) 5 58(220) 170 (11) 650 (41)175 P 15.1(384)26.5(673)34.9(886)70(1778) 6 71(269) 200 (13) 780 (49)185 S 25.5(648)25.5(648)17.7(450)56.8(1443) 5 48(182) 130 (8) 520 (33)185 H 14.1(358)25.5(648)61.5(1562)56.7(1440) 5 48(182) 130 (8) 520 (33)185 P 15.3(389)26.7(678)117.3(2979)56.1(1425) 5 58(220) 170 (11) 650 (41)175 C 15.1(384)26.53(674)1.7(43)38.1(968) 6 71(269) 200 (13) 780 (49)210 S 14.1(358)25.5(648)61.6(1565)58.8(1494) 5 48(182) 130 (8) 520 (33)210 H 15.1(384)26.5(673)34.9(886)70(1778) 6 71(269) 200 (13) 780 (49)210 P 15.3(389)26.7(678)78.9(2004)70.3(1786) 6 71(269) 200 (13) 780 (49)TABLE 9 - OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATORNOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are permitted.Glycol limits are higher. Please contact your Quantech Sales Representative for ratings and further information.