Controls and ComponentsUnits are supplied with a wireless remote controller, which communicates with the unit Microprocessor controllerThe return air temperature sensor mounted on the unit then controls the unit operationHeat Pump units require the defrost sensor connecting between the Outdoor & Indoor units prior to operationSeveral modes of operation are available to the end user depending on the type of comfort requiredAll unit operating functions are controlled via the remote controllerUnit operating modes are : Auto, Cool, Dry, Fan and Heat (Heat Pump only)Optional Controls and ComponentsLow Ambient Controller : ICM 326H must be used in Data Room or Commercial applicationsFor a wiring diagram please contact Quietside or follow general diagram supplied with ICM ControllerProbe must be located in the fin pack or on a return bend that measures approx 100 DegF during normaloperationCondensate Pump : Field Installed Mini Pump, Quietside recommend the Aspen brand of CondensatePump, follow their wiring diagram recommendations. This pump is installed externally to the unitFollow Instructions, failure to follow instructions may causepossible malfunction and void any warrantyStep 1Remove Indoor and Outdoor units from the carton/boxIndoor unit carton contains Remote Control, Batteries and 25ft Defrost Sensor interconnect wire (HP only)Ensure these are kept in a safe place during the installation process.Step 2Locate area to Install Indoor unitIndoor unit must be located a minimum of 4ft from the floor and 4" from the ceilingChoose an area where the wall is plumb and determine how to best to run the unit interconnects4" from ceiling8" from wall 8" from wallMinimum 4ft from floorOptimum 6ft plus from floorEnsure no obstacles to Airflow are directly in front of the unit, for a minimum of 12ft for 9/12,000 Btu/h unitsand 16ft for 18/24,000 Btu/h unitsDo not install the Indoor unit units in areas exposed to high humidity (RH of 80% plus), direct sunlight anddirect heat from stoves or other devicesInstallation and Maintenance ManualUnit InstallationIndoor Unit