57SECTION N: PRE-START-UPFILL THE SYSTEM:1. Close manual and automatic air vents and drain cock.2. Fill to correct system pressure. Correct pressure will vary with each application.3. Open automatic air vent two turns.4. Slowly feed water to boiler.5. Starting on the lowest floor, open air vents one at a time until water squirts out. Close vent.6. Repeat with remaining vents.7. Close manual water feed valve when correct boiler pressure is reached.INSPECT VENTING SYSTEM:1. Check all vent pipe connections and flue pipe material.2. Ensure vent terminations are installed per code and are clear of all debris or blockage.FOR YOUR SAFETY READ BEFORE LIGHTINGWARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property dam-age, personal injury or loss of life.1. This appliance does have an intermittant pilot. It is equipped with an ignition device which automatically lights thepilot. Do Not try to light the pilot or burner by hand.2. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because somegas is heavier than air and will settle on the floor.3. WHAT TO DO IF YOU SMELL GASï Do not try to light any appliance.ï Do not touch any electrical switch; do not use any telephone in your building.ï Immediately call your gas supplier from a neighbor's telephone. Follow the gas supplier's instructions.ï If you cannot reach your gas supplier, call the fire department.4. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not turn by hand, donot try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.5. Do not use this appliance if any part has been under water, immediately call a qualified service technician to inspectthe appliance and to replace any part of the control system and any gas control which has been under water.PRE-START-UP CHECK1. Verify boiler is filled with water.2. Check system piping for leaks. If found, repair immediately.3. Vent air from system. Repeat steps 4 and 5 under ìFill the System.î Air in system can interfere with watercirculation and cause improper heat distribution.