4 | ENRIS 400-700 P EKO 3.0 v2019.06Warning!• If the device is installed in a cold environment, make sure that all connections and tubes are properly isolated. Intake and discharge airducts should be isolated in all cases.• Openings of the ducts should be covered during transportation and installation.• Make sure not to damage the heater when connecting the piping of the water heater. For tightening up, use a wrench/spanner.Before starting the equipment• make sure, that there are no strange objects inside;• manually check whether fans are not stuck or blocked;• if rotary heat exchanger is installed in the device, make sure that it is not stuck or blocked;• check the grounding;• make sure that all components and accessories are connected in accordance with the project or provided instructions.Danger: FumesSalda Antifrost system uses dis-balancing of the air flow and it may cause negative pressure in premises. Great care should be takenwhen using at the same time in premises as another heating appliance what depend on the air in premises. Such appliances includegas, oil, wood or coal-fired boilers and heaters, fireplaces, continuous flow or other water heaters, gas hobs, cookers or ovens whichdraw air in from the room and duct exhaust gases out through a chimney or extraction ducting. The heating appliance can be starvedof oxygen, impairing combustion. In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting backinto the room. In this case we strictly recommend to turn off Salda Antifrost and use an external preheater for heat exchanger anti-frostprotection (see Salda Antifrost function on the Remote controller manual).4. DIMENSIONS AND WEIGHTLWHD/D1*dW1*W2d*L1L2H1L3D1*DL4*RIS P EKO 3.0L L1 L2 L3 L4* H H1 W W1* W2 øD øD1* ød* ød[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]400 670 183 183 99 330 148 1300 - 1361 200 - - 16700 970 242 242 485 104 358 160 1380 - 1461 250 - - 16RIS EKO 3.0 400PE 0.9 400PE 1.6 400PE 3.0 400PW 700PE 1.2 700PE 3.0 700PE 4.5 700PW[kg] 74 74 74 73 103,5 104 104,5 1035. ELECTRICAL DATARIS EKO 3.0 400PE 0.9 400PE 1.6 400PE 3.0 400PWHeater - phase/voltage [50 Hz/VAC] ~1 ~1 ~1 AVS 200- power consumption [kW] 0,9 1,6 3,0Fans- phase/voltage [50 Hz/VAC] ~1 ~1 ~1 ~1exhaust - power/current [kW/A] 0,085/0,73 0,085/0,73 0,085/0,73 0,085/0,73- speed [min-1] 3200 3200 3200 3200supply - power/current [kW/A] 0,085/0,73 0,085/0,73 0,085/0,73 0,085/0,73- speed [min-1] 3200 3200 3200 3200- control input [VDC] 0-10 0-10 0-10 0-10- protection class IP54 IP54 IP54 IP54Total power consumption - power/current [kW/A] 1,07/5,5 1,77/8,5 3,17/14,5 0,17/1,5