8-5Module 5 – Connected Fan Coil ControlsOperationSection 8AWAY ModeFan Coil Thermostat terminals Ts and Tc are used to initiate or terminate an Away state in the device TheTs/Tc contact closure is configured by P16 as a Normally Open or Normally Closed contact, or as an inputto be ignoredP16 Ts/TcStatusP210 (Setback Mode) 1(Off Mode)0 (Disabled) Ignored Inactive Inactive1 (Normally Closed) Open Setback OffClose Inactive Inactive2 (Normally Open) Open Inactive InactiveClose Setback OffA contact state change detected between the two terminals will initiate the Away timers (P19 or P20)and once the timers expire, the device will enter or exit AWAY mode (indicated by the “person indoorway” icon) The timers are canceled if the contact input changes while the timers are activeIf Setback is selected when in AWAY mode (P21), the Setback set points (P17 and P18) will be in effect(indicated by “leaf” icon), overriding any schedules