Samsung Electronics 4-9• Even if you set the Use of drain pump (SEG8) option to 0, it is automatically set to 2 (the drain pump is used with 3 minute delay).• If you set the Maximum filter usage time (SEG18) option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).• If you set the Individual control with remote control (SEG20) option to a value other than 0 to 4, it is automatically set to 0(Indoor 1).• Default value of Heating setting compensation (SEG21) is 5°C for 360 cassette model.* Level control: The centralized controller can limit the functions and inputs of connected products with this functionenabled. (Example: Operation mode limit (Cooling only/Heating only/No limitation), Heatingtemperature upper limit, Cooling temperature lower limit)To enable 'Level control' when applying the DPM with the centralized controller, appoint the master (Set'Use of external control [SEG14] option to 4 or higher).Example: When installing DPM (1 Outdoor unit with 4 indoor units)Condition SEG14 Setting ResultExternal control Level control Indoor 1 Indoor 2 Indoor 3 Indoor 4Default Not set (0) Slave (All)Disuse Use 4 Not set (0) Not set (0) Not set (0) Master (Indoor 1), Slave(Indoor 2,3,4)Use (Indoor 3) Disuse Not set (0) Not set (0) 1~3 Not set (0) Slave (All)Use (Indoor 4) Use Not set (0) Not set (0) Not set (0) 5~7 Master (Indoor 4), Slave(Indoor 1,2,3)4-1-4 Changing the addresses and options individuallyWhen you want to change the value of a specific option, refer to the following table and follow the steps in Commonsteps for setting the addresses and options on page >.Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Function Page Mode Option mode tochangeTens positionof the optionnumberUnits positionof the optionnumberNew valueIndicationand detailsIndication Details Indication Details Indication Details Indication Details Indication Details Indication Details0 D Optiontype 0 to FTenspositionvalue0 to 9Unitspositionvalue0 to 9 Newvalue 0 to FExample: Changing the Buzzer control (SEG17) option of the installation options to 1 disuse.Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Function Page Mode Option mode tochangeTens positionof the optionnumberUnits positionof the optionnumberNew valueIndication 0 D 2 1 7 1