PROBLEM SOLUTIONThe air conditionerdoes not turn on oroff with the wiredremote control.• Check if you set the wired remote control for groupcontrol. If the wired remote controller is usedfor group control, air conditioners connected tothat wired remote controller will turn on or off insequence and it may take some time (Maximum32 seconds).The wired remotecontrol does notoperate.• Check if TEST indicator is displayed on the wiredremote control. If so, turn off the unit and switch offthe circuit breaker. Call your nearest service center.Operation rangesThe table below indicates the temperature and humidity ranges the air conditioner can be operated within. Refer to the tablefor efficient use.MODE OPERATIONAL TEMPERATURE INDOOR HUMIDITY IF OUT OF CONDITIONSCOOLING 20 ˚C to 52 ˚C 80 % or lessCondensation may occur on the indoorunit with risk to have either water blow offor drops on the floor.HEATING -5 ˚C to 15 ˚C - Internal protection triggers and the airconditioner will stop.VENTILATING 5 ˚C to 52 ˚C - -❋ Protective operation may start when the temperature is over 48 ˚C.❋ Heating or fan operation will be stopped when the temperature is lower than -5 ˚C.A fresh duct controls discharge temperature.Depending on indoor/outdoor temperature or installation condition, actual discharge temperature may not be exactlycontrolled.Model specification (weight and dimension)Type Model Net weight Net dimension (W x D x H)Indoor unitAM140JNEPEHAM140JNEPEH/EU 51.0 kg 1110 x 390 x 650 mmAM220JNEPEHAM220JNEPEH/EU 85.0 kg 1240 x 470 x 1040 mmAM280JNEPEHAM280JNEPEH/EU 85.0 kg 1240 x 470 x 1040 mm03 OTHERSEnglish-17