10Installation locationMoving the Outdoor UnitX Select the moving route in advance.X Be sure that moving route is safe from the weight of the outdoor unit.X Do not slant the product more than 30˚ when carrying it. (Do not lay the product down sideways.)X The surface of the heat exchanger is sharp. Be careful not to get injured while moving and installing.When moving with a crane or wire ropeX When moving an outdoor unit to a higher place such as the rooftop.- Fasten the wire rope as seen in the picture.- Move the outdoor unit with the product packed to prevent possible productdamage during the transportation.Wire rope/strapsWood paletteWhen moving an outdoor unit with handsX Moving the outdoor unit by lifting up and carrying due to the short travel distance.- Two people should carry the outdoor unit by holding transportation handle.- Be careful not to damage the heat exchanger of the rear side of the outdoor unit duringtransportation.- Be careful not to get hurt by the sharp surface of the heat exchanger.Installation and base ground work for an outdoor unitX Install the outdoor unit 150mm (6 inch) higher than the base ground and install the drain hole to connect the pipe to thedrainage.X When the front fan of an outdoor unit is installed in a place where the average snowfall is more than 150mm (6inch), thedischarge duct should be attached to the outdoor unit.X The concrete foundation should be 1.5 times larger than bottom of the outdoor unit.X It is necessary to install wire mesh or steel bar when outdoor units are installed on a soft foundation.X When installing multiple outdoor units at the same place, install theH beam on the base ground.(When installing a number of outdoor units, you can install it on thebase ground.)X Install the H beam [150mm (6 inch) x 150mm (6 inch) x t10 : basicspecification] or vibration absorption frame to jut out from the baseground.X After installing the H beam, apply corrosion protection.X Install a square pad [t=20mm (1 inch) or more] to prevent vibrationfrom the outdoor unit onto the base ground. Place the outdoor uniton the H beam and fix it with the bolt, nut and washer. (Fix with M10basic anchor bolt, nut and washer.)Outdoor unitAnchor boltNut, SpringwasherH beamSquare padA+10~20mm(0.5~1 inch) or moreA20mm(1 inch)75mm(3inch)or more