General OverviewSamsung Electronics 112-2 Model names of Indoor/Outdoor Unit2-2-1 Indoor UnitModelCapacity ( kW )2.2 2.8 3.6 5.6 7.1 9.0 16.0Hydro unitSlim ductMSP ductRAC(Notinclude EEV)Console1. Make sure to use an indoor unit that is compatible with EHS TDM PLUS.2. Indoor units can be connected within the range indicated in following table.3. If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of theindoor unit may decrease.4. Total capacity of the connected indoor units can be allowed from 50% to 100% of the total outdoor unit capacity.0.5 x Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor unit ≤ 1.0 x Σ (Outdoor unit capacity)5. You can connect maximum 7 indoor units to the outdoor unit.Maximum quantity of connectable indoor unit is set to 7 since outdoor unit only support up to 7 communication address. Indoor unitaddress can be assigned from 0~7.