System Sensor 5151 Installation And Maintenance Instructions Manual
SS-400-011 1 I56-5151-001INSTALLATION AND MAINTENANCE INSTRUCTIONS3825 Ohio Avenue, St. Charles, Illinois 601741-800-SENSOR2, FAX: 630-377-6495www.systemsensor.com5151 Plug-In Heat DetectorSPECIfICATIONSHeight: 1.64 inches (42 mm)Diameter: 4.0 inches (102 mm)Weight 2.8 oz. (80g)Operating Temperature Range: 32° to 100°F (0° to 38°C)Operating Humidity Range: 10% to 93% Relative Humidity noncondensingOperating voltage: 8.5 to 35VDCStandby Current: 80μA @24VDCAlarm Current: 10mA Min. 130mA Max. (Must be limited by control panel)Latching Alarm: Reset by momentary power interruptionSensitivity: 135°F (57°C) Fixed or 15°F/min rate-of-riseBEfORE INSTALLINGThis detector must be installed in compliance with the control panel installa-tion manual and meet the requirements of the authority having jurisdiction.Inaddition, the National Fire Protection Association has published codes, stan-dards, and recommended practices for the installation and use of detectors,NFPA 72.Therefore, the installer must be familiar with these requirements, with localcodes, and any special requirements of the authority having jurisdiction.NOTICE: This manual should be left with the owner/user of this equipment.IMPORTANT: The detector must be tested and maintained regularly followingNFPA 72 requirements. The detector should be cleaned at least once a year.GENERAL DESCRIPTIONThe 5151 is a rate-of-rise with fixed temperature alarm, conventional 2-wirethermal detector. This detector is designed to provide open area protectionwith 50-foot spacing capability as approved by UL 521, RTI rating is classifiedas FAST in accordance with FM 3210.Two LEDs on each detector provide local 360° visible alarm indication. Theyflash every five seconds indicating that power is applied and the detectoris working properly. The LEDs latch on in alarm. LEDs will be off when atrouble condition exists indicating that the detector sensitivity is outside thelisted limit. Remote LED annunciator capability is standard and may be imple-mented through an optional accessory RA100Z. The alarm can be reset onlyby a momentary power interruption. This detector may be tested by activatingthe internal reed switch with a magnet.BASE WIRING GUIDERefer to the installation instructions for the plug-in detector base for electricalspecifications and wiring instructions. The base provides screw terminals forpower and remote annunciator connections.INSTALLATIONNOTE: All wiring must conform to applicable local codes, ordinances, andregulations.NOTE: Verify that all detector bases are installed, that the initiating-devicecircuits have been tested, and that the wiring is correct. (Refer to detector basemanual for testing procedure.)WARNINGRemove power from initiating-device circuits before installing detectors.1. Install detectors:a. Place the detector into the detector base.b. Turn the detector clockwise until the detector drops into place.c. Continue turning detector clockwise to lock it in place.2. Tamper Resistance:The detector bases can be made tamper resistant. When capabilityis enabled, detectors cannot be removed from the base without theuse of a tool. See the detector base installation manual of the detectorbase for details in using this capability.3. After all detectors have been installed, apply power to the control unit.4. Test the detector using the magnet as described under TESTING.5. Reset the detector at the system control panel.6. Notify the proper authorities that the system is back on line.TAMPER RESISTANCEThe detector bases include a feature that, when activated, prevents removalof the detector without the use of a tool. Refer to the installation instructionmanual of the detector base to make use of this capability.TESTINGBefore testing, notify the proper authorities that the smoke detector system isundergoing maintenance and will temporarily be out of service. Disable thezone or system undergoing maintenance to prevent unwanted alarms. Detec-tors must be tested after installation and as part of periodic maintenance. Test5151 as follows:NOTE: Before testing the detector, check to ensure the LEDs blink. If they donot, the detector has lost power (check the wiring), it is defective (return it forrepair), or the detector sensitivity is outside the listed limits.A. Test Magnet (p/n M02-04-01 or M02-09-00)1. Place the magnet against the cover in the location designated by theraised mark to activate the test feature (see Figure 1).2. The LEDs should latch ON within 5 seconds indicating alarm and annun-ciating the panel.B. Direct Heat Method (Hair dryer of 1000-1500 watts)1. A hair dryer of 1000-1500 watts should be used to test the thermistor.Direct the heat toward the thermistors, holding the heat source approxi-mately 12 inches from the detector in order to avoid damaging the plastichousing.2. The LEDs on the detector should light when the temperature at the de-tector reaches the set point.3. Reset the detector at the system control panel. The detector will resetonly after it has had sufficient time to cool.Notify the proper authorities that the system is back on line.Detectors that fail these tests should be cleaned as described under MAIN-TENANCE and retested. If the detectors still fail these tests, they should bereturned for repair.MAINTENANCENOTE: Before cleaning notify the proper authorities that the system is under-going maintenance, and therefore the system will temporarily be out of ser-vice. Disable the loop or system undergoing maintenance to prevent unwantedalarms.It is recommended that the sensor be removed from its mounting base foreasier cleaning and that sensors be cleaned at least once a year. Use a vacuumcleaner to remove dust from the sensing chamber.I56-5151-001 |
Related manuals for System Sensor 5151
System Sensor 2151 Installation And Maintenance Instructions Manual
System Sensor 5451 Installation And Maintenance Instructions Manual
System Sensor 1451 Installation And Maintenance Instructions Manual
System Sensor EBR Installation And Maintenance Instructions Manual
System Sensor WFD Installation And Maintenance Instructions Manual
System Sensor 1424 Installation And Maintenance Instructions Manual
System Sensor WFDT Installation And Maintenance Instructions Manual
System Sensor WFDT Installation And Maintenance Instructions Manual
System Sensor 6424 Installation And Maintenance Instructions Manual
System Sensor B501 Installation And Maintenance Instructions Manual
This manual is suitable for:
manualsdatabase
Your AI-powered manual search engine