8 Enclosure8.1 Technical dataType FRQS-4A FRQS-10A FRQS-16APart-No. 36231(308276-42)36232(308277-42)37275(308300-42)Rated current output {1} 4 A 10 A 16 ARated current input {2}(I fundamental component @ 50 Hz)3.8 A(3.5 A)9.4 A(8.6 A)15.2 A(14.0 A)Recommended motor output {3} 1.5 kW 4.0 kW 7.5 kWMax. line fuse {4} 10 A 16 A 20 AMax. leakage current according to the denednetworks of DIN EN 60990 (depending onconnected line voltage *)< 3.5 mA < 3.5 mA < 3,5 mA @ < 480 V *≥ 3,5 mA @ ≥ 480 V *Max. heat dissipation approx. {2} 80 W 200 W 360 WRated temperature 55 °C 40 °C 40 °CWeight 5.4 kg 6,3 kg 7.0 kg{1} Rated current output current indication rating plate @ rated voltage, @ rated temperature(cos φ 0.8 at the output){2} At rated voltage (cos φ 0.8 at the output), values for different specifications on request.{3} Example for power of a 4 pole motor. For the dimension of the frequency inverter size the ratedcurrent of the motor is crucial!{4} Max. supply side line fuse according to DIN EN 60204-1 classification VDE0113 chapter 1Line voltage* 3 ~ 208...480 V (-15 up to +10 %), 50/60 HzRated voltage 400 VMaximal output voltage approx. 95 % from ULineMaximal output frequency 50 HzEdgefrequency 48.5 HzU/f-characteristic curve squareSwitching frequency 16 kHzRampup time 20 secRampdown time 20 secCurrent limit FRQS-4A: 120 %, FRQS-10A: 110 %, FRQS-16A: 120 %Power factor > 0.9Input resistance for speed settingsignalfor 0... 10 V input: Ri > 100 kΩfor 0...20 mA input: Ri = 100 ΩVoltage supply for external devi-ces+24 V ± 20 %, Imax 70 mAHeat dissipation in standby opera-tionapprox. 3 WOperating Instructions FRQS-4/10/16A EnclosureL-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-4222/27