9www.Ultra-Aire.com | 1-800-533-7533 Ultra-Aire 70H Installation InstructionsThe Ultra-Aire 70H generates condensate.Place a secondary drain pan under the dehumidifier if it is suspended above a finished area or above anarea where water leakage could cause damage.A drain trap is required for the dehumidifier to run properly. Install a 3/4" threaded male NPT adapter to thedrain pan. Install a drain pipe assembly utilizing 3/4" PVC pipe to transport the condensate to a drain. Pitchof drain should be 1" per 10'.An optional condensate pump kit is available for use with the Ultra-Aire 70H and may be installed if lift isrequired to dispose of condensate. Condensate is automatically pumped to a remote location when thewater level in the pump’s reservoir rises to close the float switch.The pump also contains a safety float switch. The white leads from this switch extend from beneath thepump cover. This switch should be installed in series with the field wire that connects to the common leadfrom the Ultra-Aire 70H to the control panel. If the pump fails, this switch opens the common control circuitand stops water production before the reservoir overflows. Contact a qualified electrician to install the safetyfloat switch to the Ultra-Aire 70H dehumidifier.Note: An optional condensate pump kit can be purchased from a local dealer or online.DRAIN INSTALLATIONDrain InstallationFront ViewSecondary Drain PanDrain PortDrain Trap