3* Parameters ALFA 71 MODPara-meterDescription Parameter Range Default01 Function thermostat 1=Cool2=Heat102 Offset temperature sensor-1 -15.0..+15.0C 0.01011121314P-bandI-timeRuntime valveReset timeReset to minimum or maximum valveposition0,0..+15,0C0..99 Minutes0..999 Seconds0..999 Minutes0 = mimimum1 = maximum5,00120600202122Minimum setpointMaximum setpointRead-out above -10C per 1C-50,0..+50,0-50,0..+50,00= no, 1= yes-50,0+50,003031323334353637Alarm typeMinimum alarm setpointMaximum alarm setpointTime delay minimum alarmTime delay maximum alarmRelay function alarm relayReset alarm relay after recoveringalarmReset alarm relay after manual reset0= None1= Absolute2= Relative-50.0..+50.0C-50.0..+50.0C0..99 min.0..99 min.0= Watch alarm1= Control alarm0= No, 1= Yes0= No, 1= Yes1-50+50000004041Start up delay after power failureForced relay function at sensor failure0..99 Minutes0= None1= Min.2= Max.0052 Time correction (at realtimeclock /network)-99..99 Minutes 090 Network number (at network version) 1..31 19596979899Software versionProduction yearProduction weekSerial number (x1000)Serial number (units)0..25500..991..520..2550..99900100