6vacon • 29 CommunicationsTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2056.1.1 Binary Value ObjectTable 14.InstanceID Object Name Description Inactive /ActivePresentValueAccessTypeBV0 Ready State Indicates whether the driveis ready or notNot Ready /Ready RBV1 Run/Stop State Indicates whether the driveis running or stopped Stop / Run RBV2 Fwd/Rev State Indicates the rotationdirection of the motor Fwd / Rev RBV3 Fault State Indicates if a fault is active OK / Fault RBV4 Alarm State Indicates if an alarm isactive OK / Alarm RBV5 At Setpoint Ref. Frequency reached False / True RBV6 At Zero Speed Motor Running at zerospeed False / True RBV7 fb_ProcessdataOut_01 Bit_0 ProcessDataOut1 bit 0 0 / 1 RBV8 fb_ProcessdataOut_01 Bit_1 ProcessDataOut1 bit 1 0 / 1 RBV9 fb_ProcessdataOut_01 Bit_2 ProcessDataOut1 bit 2 0 / 1 RBV10 fb_ProcessdataOut_01 Bit_3 ProcessDataOut1 bit 3 0 / 1 RBV11 fb_ProcessdataOut_01 Bit_4 ProcessDataOut1 bit 4 0 / 1 RBV12 fb_ProcessdataOut_01 Bit_5 ProcessDataOut1 bit 5 0 / 1 RBV13 fb_ProcessdataOut_01 Bit_6 ProcessDataOut1 bit 6 0 / 1 RBV14 fb_ProcessdataOut_01 Bit_7 ProcessDataOut1 bit 7 0 / 1 RBV15 Run/Stop CMD Command to start drive(FB control is active) Stop / Run CBV16 Fwd/Rev CMD Command to run forward/reverse Fwd/Rev CBV17 Reset Fault Command to reset ActiveFault from drive 0 / Reset CBV18 Stop By Coast Stop Drive by coast 0 / 1 CBV19 Stop By Ramp Stop Drive by ramp 0 / 1 CBV20 Quick Stop Quick Stop 0 / 1 CBV21 Zero Ramp Stop by zero ramp 0 / 1 CBV22 Hold Ramp Hold ramp 0 / 1 CBV23 BusCtrl Activate Bus control 0 / 1 CBV24 BusRef Activate Bus reference 0 / 1 CBV25 fb_control_word Bit_10 fb_control_word bit 10 0 / 1 CBV26 fb_control_word Bit_11 fb_control_word bit 11 0 / 1 CBV27 fb_control_word Bit_12 fb_control_word bit 12 0 / 1 C