Modbus/tcp vacon • 1324-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com44. COMMISSIONINGThe Vacon EtherNet/IP board is commissioned with the control keypad by giving values toappropriate parameters in menu M7 (or with NCIPConfig tool, read chapterIP ToolNCIPConfig). Keypad commissioning is only possible with NXP- and NXS-type frequencyconverters, not possible with NXL-type frequency converters.Expander board menu (M7)TheExpander board menu makes it possible for the user to see what expander boards areconnected to the control board and to reach and edit the parameters associated with theexpander board.Enter the following menu level (G#) with theMenu button right. At this level, you can browsetrough slots A to E with theBrowser buttons to see what expander boards are connected. Onthe lowermost line of the display you see the number of parameter groups associated with theboard. If you still press theMenu button right once you will reach the parameter group levelwhere there are one group in the Ethernet board case: Parameters. A further press on theMenu button right takes you to Parameter group.Ethernet/IP parameters# Name Default Range Description1 Comm. Timeout 10 0…255 s 0 = Not used2 IP Part 1 192 1…223 IP Address Part 13 IP Part 2 168 0…255 IP Address Part 24 IP Part 3 0 0…255 IP Address Part 35 IP Part 4 10 0…255 IP Address Part 46 SubNet Part 1 255 0…255 Subnet Mask Part 17 SubNet Part 2 255 0…255 Subnet Mask Part 28 SubNet Part 3 0 0…255 Subnet Mask Part 39 SubNet Part 4 0 0…255 Subnet Mask Part 410 DefGW Part 1 192 0…255 Default Gateway Part 111 DefGW Part 2 168 0…255 Default Gateway Part 212 DefGW Part 3 0 0…255 See Ch. 713 DefGW Part 4 1 0…255 See Ch. 714 InputAssembly --NOT USED15 OutputAssembly --NOT USEDTable 2. Ethernet parametersIP AddressIP is divided to 4 parts. (Part = Octet) Default IP Address is 192.168.0.10.Communication timeoutDefines how much time can pass from the last received message from the Client Device beforefieldbus fault is generated. Communication time out is disabled when given the value 0.Communication timeout value can be changed from the keypad or with NCIPConfig tool (readchapterIP Tool NCIPConfig).