6 • vacon TECHNICAL SPECIFICATIONSTel: +358-201-2121 • Fax: +358-201-212 2052. TECHNICAL SPECIFICATIONS2.1 Inverter ratingsRange of input voltages 340-800Vcc, 50 Hz, 3~InvertertypeNom. outputpower[kW]Recommendedmax PV power[kW]Max al-lowed PVpower[A]Max effi-ciency [%]Power con-sumption atnight[W]Inverterdimensions[mm]Inverterweight[kg]NXV0010 10 12 50 >94% <5 600x1481x600 220NXV0015 15 18.5 50 >94% <5 600x1481x600 220NXV0020 20 24 99 >94% <5 600x1481x600 300NXV0025 25 30 99 >94% <5 600x1481x600 300NXV0030 30 36 99 >94% <5 600x1481x600 300NXV0040 40 48 198 >95% <30 800x1881x600 550NXV0050 50 60 198 >96% <30 800x1881x600 550NXV0080 80 96 353 >96% <30 800x2281x600 850NXV0100 100 120 353 >96% <30 800x2281x600 850Table 2-1. Power ratings, dimensions and weights2.2 Technical dataDC Input Range of input voltages 340...800 VDCMaximum input voltage 900 VDCAC Output Mains voltage 3*400 ± 10%Galvanic isolation For each isolator transformer attachedFrequency 50/60 Hz ± 0,5%Cos φ >0.99, for output 20%-100% of PnHarmonic distortion < 2.5% for output > 30% of powerConsumption at night < 5W (NXV0010...NXV0030); <30 W (NXV0040...NXV0100)Maximum efficiency > 94...96%Ambient temperature -10...+40°C; 1-% derating for each degree up to 50°C requiredRelative humidity < 95% no condensationProtection IP21Display Alfanumeric display per unit with two lines of 14 characters, ledsindicating functioning, plus fault and function push buttons.Signalling 3 potential free contacts to indicate faults and alarmsCommunications May include one of the following communication buses as an op-tional feature: Modbus RTU, Ethernet (Modbus/TCP), RS485, GPRS,string and inverter monitoringMay include a monitoring system with http-access as an optionalfeature.IEC61000-3-3 For the product to meet the technical requirements of IEC 61000-3-3, the supply should have a system impedance accordingly:≤ NXV0015: Zsys = 0.105 ohm≤ NXV0030: Zsys = 0.270 ohm≤ NXV0050: Zsys = 0.176 ohm≤ NXV0100: Zsys = 0.136 ohmAmbient condi-tionsAltitude Max. 2,000mEnvironmental category Indoor, conditionedPollution degree PD2OvervoltagecategoryAC (Mains) OVCIIIDC (Panels) OVCIITable 2-2. Technical data