Operating and installation manual for VR 61 mixer module105 AssemblyThe mixer module VR 61 is wall-mounted in proximitywith the associated function units .The adjustment of all required parameters is carried outusing the controller VRC 430 or VRC 430f via eBUS. Allconnections of the associated function units take placedirectly on the mixer module VR 16 via ProE terminals.5.1 Scope of deliveryBefore starting the installation, check the scope ofdelivery for completeness and lack of damage.Pos. Number Component1 1 Mixer module VR 612 1 VR 10 standard sensor3 1 Mounting accessories (screws, plugs)Table 5.1 Scope of delivery of the mixer module VR 61h Note!Depending upon the configuration of the heatingsystem, additional sensors may be required asstorage tank sensors.Only the standard sensor VR 10 from theVaillant accesories programme should be used.The heating control using Vaillant componentsis matched to the sensor characteristic curveof the VR 10.Temp. in °C R in kOhm Temp. in °C R in kOhm10 5,363 55 0,80615 4,283 60 0,67120 3,372 65 0,56225 2,700 70 0,47330 2,176 75 0,39935 1,764 80 0,33940 1,439 85 0,28845 1,180 90 0,24750 0,973Table 5.2 Standard sensor VR 10, allocation temperaturemeasurement value5.2 Assembling VR 61 mixer moduleFig. 5.1 Opening the casing⇒ Release the screw on the top of the casing .⇒ Tilt the casing cover forwards slightly and remove.12Fig. 5.2 Fitting the mixer module VR 61Key1 Mounting apertures2 Cable brackets5 AssemblyAll manuals and user guides at all-guides.comall-guides.com