6 © VALLOX • We reserve the right to make changes without prior notice.What the units include can vary depending on the sales area.Vallox121SE4. Week-clock control4.1 Week programme programmingThe week programme can be used to set the desired fan speed (base fanspeed) and supply air temperature for each hour of the day on seven daysa week. The week programme overrides manual adjustments.Carbon dioxide and humidity adjustment can increase fan speed but neverdecrease it below the base fan speed set in the week programme.Example: MondayIt is the intention to decrease fan speed to speed 2 and supply air tempera-ture to 17 ºC between 07:00 (7 a.m.) and 16:00 (4 p.m.). After that, fanspeed is raised to speed 4 and supply air temperature to 20 ºC. For theevening, fan speed is boosted to speed 6 between 19:00 and 21:00 (7p.m. and 9 p.m.), after which fan speed is lowered back to 4.4.2 Adjusting time© VALLOX • We reserve the right to make changes without prior notice.5. Factory settingsBase fan speed = 1Maximum fan speed = 8Carbon dioxide adjustment (CO2) = 900 ppm CO2Adjustment interval = 10 minWinter parameter A = 9 barsWinter parameter B = 9 barsMode of melting = stopping of fanMaintenance reminder = 4 monthsCell bypass = 12 °CCascade adjustment = not in useSpeed steps:1. = 31 %2. = 42 %3. = 47 %4. = 54 %5. = 59 %6. = 66 %7. = 72 %8. = 100 %Humidity level (Rh level) setting = automaticSwitch type = fireplace switch3.24 Choosing maximum fan speedMAX speed8The desired maximum fan speed isselected with the + and – buttons.Maximum fan speed is on either withadjustments or always. See Section3.25. Mode of operation of maximumspeed setting.3.25 Mode of operation of maximum speed settingMAX speed limitwith adjustmentsThe maximum fan speed setting canbe selected to be active either only inconnection with (carbon dioxide andhumidity) sensor adjustments or perma-nently. The selection is done with the +and – buttons.3.26 Adjusting fan on the supply air sideDC fan, supply100%The desired adjustment value for thesupply air fan is selected with the +and – buttons. The rotation speed ofthe supply air fan can be decreasedby decreasing the percentage.OPERATING INSTRUCTIONS FOR CONTROL PANELMove the cursor with the arrow keys andchange values with the + and – buttons.Note that to exit and save when theprogramming is finished, move the cursorbelow the word Exit and press + or –.Changes in fan speed (Sp.) and supplyair temperature (Temp.) are only made forthe hours desired; in other cases, use N(no change to previous).Monday (D=1), 07:00 (H=7), fan speed2 (Sp. = 2), supply air temperature 17°C (Temp =17).Move the cursor to the following hour.Monday (D=1), 16:00 (H=16), fanspeed 4 (Sp. = 4), supply air temperature20 °C (Temp =20).Move the cursor to the following hour.Monday (D=1), 19:00 (H=19), fanspeed 6 (Sp.=6), supply air temperatureno change (Temp=N).Move the cursor to the following hour.Monday (D=1), 21:00 (H=21), fanspeed 4 (Sp.=4), supply air temperatureno change (Temp=N).Move the cursor to the following hour.3.27 Adjusting fan on the extract air sideDC fan, exhaust100%The desired adjustment value for theextract air fan is selected with the +and – buttons.The rotation speed of the extract air fancan be decreased by decreasing thepercentage.3.28 Fan speed level adjustmentSpeed 1 level15%The desired fan speed level is adjustedfrom the menu. Adjustment range is0–100%. However, fan speeds limitthe adjustment range as follows:If for instance speed 3 is 30%, speed 2 cannot be increased to morethan 29% and speed 4 cannot be decreased below 31%.The fan stops when the setpoint is 14% or lower. The adjustment is madewith the + and – buttons. There are 8 displays, one for each fan step.3.29 Moving to Operating menuTo Main menupress + and –To move back to the Operating menu,press the + and – buttons simultaneous-ly.Similar changes have to be made separately for each day. Finally, exit theprogramming mode by selecting Exit. If you wish, you can erase the weekprogramme as indicated in Section 3.6. You can then start programmingfrom the start. You can see the settings programmed by choosing a day andby scrolling the hours with the + or – button.Move the cursor with the arrow keys andchange values with the + and – buttons.Exit and save when the programming isfinished.Monday (D=1), hours 15 (H=15), minu-tes (M=30)Time is maintained even though there isa power failure. (See Section 1.1, figureitems 5 and 6).d hr sp tmp1 0 N N Exitd hr sp tmp1 7 2 17 Exitd hr sp tmp1 16 4 20 Exitd hr sp tmp1 19 6 N Exitd hr sp tmp1 21 4 N ExitCursorD Day 1…71 = Monday, 2 = Tuesday etc.H Hour0…23Sp. Fan speed1…8Temp Supply air temperature10…30°CExit Save the setting and exitN No change to previous hour settingCursorD Day 1…71 = Monday, 2 = Tuesday etc.H Hour, 0…23M Minutes, 0…60Exit Save the setting and exitSTARTING POINTday hour min1 15 30 ExitThis appliance can be used by children aged from 8 years and aboveand persons with reduced physical, sensory or mental capabilities orlack of experience and knowledge if they have been given supervisi-on or instruction concerning use of the appliance in a safe way andunderstand the hazards involved. Children shall not play with the app-liance. Cleaning and user maintenance shall not be made by childrenwithout supervision.