7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, VEGACAP 62 iscompletely maintenance-free.7.2 Fault rectificationVEGACAP 62 offers maximum reliability. Nevertheless faultscan occur during operation. These may be caused by thefollowing, e.g.:l Sensorl Processl Supplyl Signal processingThe first measure to be taken is to check the output signal. Inmany cases the causes can be determined and faults quicklyrectified by doing this.Should the following measures not be successful, please callin urgent cases the VEGA service hotline under the phonenumber +49 1805 858550.The hotline is available to you 7 days a week round-the-clock.Since we offer this service world-wide, the support is onlyavailable in the English language. The service is free ofcharge, only the standard telephone costs will be charged.? VEGACAP 62 signals "covered" when the vibratingelement is not submerged (overfill protection)? VEGACAP 62 signals "uncovered" when the vibratingelement is submerged (dry run protection)l Supply voltage too lowà Check the power supplyl Electronics defectiveà Push the mode switch (A/B) on the signal conditioninginstrument. If the signal conditioning instrument thenchanges the mode, the instrument may be mechan-ically damaged. Should the switching function in thecorrect mode still be faulty, return the instrument forrepair.à Check if there is buildup on the probe, and if so,remove it.Causes of malfunctionFault rectification24 hour service hotlineChecking the switching signal22 VEGACAP 62 - with two-wire outputMaintenance and fault rectification30007-EN-060222