165 Set up the sensor with the display and adjustment moduleVEGAPULS 61 • Modbus and Levelmaster protocol47108-EN-180710If a false signal suppression has already been saved in the sensor,the following menu window appears when selecting "False signalsuppression":Delete: An already created false signal suppression will be com-pletely deleted. This is useful if the saved false signal suppression nolonger matches the metrological conditions in the vessel.Extend: is used to extend an already created false signal suppres-sion. This is useful if a false signal suppression was carried out withtoo high a level and not all false signals could be detected. Whenselecting "Extend", the distance to the product surface of the createdfalse signal suppression is displayed. This value can now be changedand the false signal suppression can be extended to this range.5.3 Menu overviewMenu item Parameter Default settingMeasurementloop nameSensorMedium LiquidWater basedApplication Storage tankVessel form Vessel top Dished formVessel bottom Dished formVessel height/Measuring range35 mMax. adjustment 0,000 m(d)100.00 %Min. adjustment 35 m0.00 %Damping Integration time 0.0 sCurrent outputmodeOutput character-istics4 … 20 mAFailure mode ≤ 3.6 mACurrent output -Min./Max.Min. current 3.8 mAMax. current 20.5 mALock adjustment ReleasedMenu item Default settingLanguage Order-specificSetupDisplay