155 Set up with the display and adjustment moduleVEGAPULS 64 • 4 … 20 mA/HART - two-wire51462-EN-160111The return to the measured value indication is carried out through the[->] or [ESC] keys or automatically after 3 sThe menu "Extended adjustment" is available for further settings. Im-portant functions are described in the following chapter. You can find acomplete description of all functions of the "Extended adjustment" inthe operating instructions manual of VEGAPULS 64.5.3 Parameter adjustment - Extended adjustmentThe main menu is divided into five sections with the following func-tions:Setup: Settings, e.g., for measurement loop name, units, application,adjustment, signal outputDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, for example, on device status, peak value,simulation, echo curveAdditional adjustments: Date/Time, reset, copy function, scaling,current output, false signal suppression, linearization, HART mode,special parametersInfo: Instrument name, hardware and software version, calibrationdate, instrument featuresIn the main menu item "Setup", the individual submenu itemsshould be selected one after the other and provided with the correctparameters to ensure optimum adjustment of the measurement. Theprocedure is described in the following.Since the radar sensor is a distance measuring instrument, thedistance from the sensor to the product surface is measured. Toindicate the actual level, an allocation of the measured distance to thepercentage height must be carried out.To perform the adjustment, enter the distance with full and empty ves-sel, see the following example:Extended adjustmentMain menuSetup - Adjustment