476 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Menu Menu item Default valueDisplay Language Like orderDisplayed value DistanceDisplay unit mScaling size VolumelScaling 0.00 lin %, 0 l100.00 lin %, 100 lBacklight Switched offAdditional adjust-mentsDistance unit mTemperature unit °CProbe length Length of the standpipe Ex factoryLinearisationcurveLinearHART mode StandardAddress 06.4 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwards. They are thusavailable for multiple use or service purposes.If the instrument is equipped with an indicating and adjustmentmodule, the data in the sensor can be saved in the indicating andadjustment module. The procedure is described in the operatinginstructions manual "Indicating and adjustment module" in the menuitem "Copy sensor data". The data remain there permanently even ifthe sensor power supply fails.The following data or settings for adjustment of the indicating andadjustment module are saved:• All data of the menu "Setup" and "Display"• In the menu "Additional adjustments" the items "Sensor-specificunits, temperature unit and linearization"• The values of the user programmable linearisation curveThe function can also be used to transfer settings from one instru-ment to another instrument of the same type. If it is necessary toexchange a sensor, the indicating and adjustment module is insertedinto the replacement instrument and the data are likewise written intothe sensor via the menu item "Copy sensor data".