4Type overviewRadar - Level measurement in bulk solids29427-EN-1603122 Type overviewVEGAPULS 67 VEGAPULS SR 68 VEGAPULS 68Applications Bulk solids Bulk solids under extremely difficult pro-cess conditionsBulk solids under extremely difficult pro-cess conditionsMax. measuring range 15 m (49.21 ft) 30 m (98.43 ft) 75 m (246.1 ft)Antenna/Material Completely encapsulated plastic horn an-tenna/PPHorn or parabolic antenna/316L Horn or parabolic antenna/316LProcess fitting/Material Mounting strap/316L or flange/PP Thread G1½/316L according to DIN 3852-A or flange/316LThread G1½/316L according to DIN 3852-A or flange/316LProcess temperature -40 … +80 °C (-40 … +176 °F) -40 … +250 °C (-40 … +482 °F) -196 … +450 °C (-321 … +842 °F)Process pressure -1 … +2 bar/-100 … +200 kPa(-14.5 … +29.0 psig)-1 … +100 bar/-100 … +10000 kPa(-14.5 … +1450 psi)-1 … +160 bar/-100 … +16000 kPa(-14.5 … +2320 psi)Deviation ±2 mm ±2 mm ±2 mmFrequency range K-band K-band K-bandSignal output • 4 … 20 mA/HART - two-wire• 4 … 20 mA/HART - four-wire• Profibus PA• Foundation Fieldbus• Modbus, Levelmaster protocol• 4 … 20 mA/HART - two-wire• 4 … 20 mA/HART - four-wire• Profibus PA• Foundation Fieldbus• Modbus, Levelmaster protocol• 4 … 20 mA/HART - two-wire• 4 … 20 mA/HART - four-wire• Profibus PA• Foundation Fieldbus• Modbus, Levelmaster protocolIndication/Adjustment • PLICSCOM• PACTware• VEGADIS 81• VEGADIS 82• PLICSCOM• PACTware• VEGADIS 81• VEGADIS 82• PLICSCOM• PACTware• VEGADIS 81• VEGADIS 82Approvals • ATEX• IEC• FM• CSA• ATEX• IEC• Shipbuilding• FM• CSA• ATEX• IEC• Shipbuilding• FM• CSA