436 Set up with the display and adjustment moduleVEGAPULS 69 • 4 … 20 mA/HART - two-wire47247-EN-170818Information:The echo curve of setup is stored automatically during the quicksetup.The return to the measured value indication is carried out through the[->] or [ESC] keys or automatically after 3 sYou can find "Extended adjustment" in the next sub-chapter.6.5 Parameter adjustment - Extended adjustmentThe main menu is divided into five sections with the following func-tions:Setup: Settings, e.g., for measurement loop name, units, application,adjustment, signal outputDisplay: Settings, e.g., for language, measured value display, light-ingDiagnosis: Information, for example, on device status, peak value,simulation, echo curveAdditional adjustments: Date/Time, reset, copy function, scaling,current output, false signal suppression, linearization, HART mode,special parametersInfo: Instrument name, hardware and software version, calibrationdate, instrument featuresIn the main menu item "Setup", the individual submenu itemsshould be selected one after the other and provided with the correctparameters to ensure optimum adjustment of the measurement. Theprocedure is described in the following.Here you can assign a suitable measurement loop name. Push the"OK" key to start the editing. With the "+" key you change the sign andwith the "->" key you jump to the next position.You can enter names with max. 19 characters. The character setcomprises:• Capital letters from A … Z• Numbers from 0 … 9• Special characters + - / _ blanksIn this menu item you select the distance unit and the temperatureunit.Main menuSetup - Measurementloop nameSetup - Units