206 SupplementVEGAPULS 69 • Profibus PA47256-EN-1708186 Supplement6.1 Technical dataNote for approved instrumentsThe technical data in the respective safety instructions are valid for approved instruments (e.g. withEx approval). These data can differ from the data listed herein, for example regarding the processconditions or the voltage supply.Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barOptions of the cable entryƲ Cable entry M20 x 1.5; ½ NPTƲ Cable gland M20 x 1.5; ½ NPT (cable ø see below table)Ʋ Blind plug M20 x 1.5; ½ NPTƲ Closing cap ½ NPTMaterial ca-ble glandMaterial sealinsertCable diameter4.5 … 8.5 mm 5 … 9 mm 6 … 12 mm 7 … 12 mm 10 … 14 mmPA NBR – ● ● – ●Brass, nickel-platedNBR ● ● ● – –StainlesssteelNBR – ● ● – ●Wire cross-section (spring-loaded terminals)Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14)Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)Voltage supplyOperating voltage UBƲ Non-Ex instrument 9 … 32 V DCƲ Ex-ia instrument - Power supplyFISCO model9 … 17.5 V DCƲ Ex-ia instrument - Power supplyENTITY model9 … 24 V DCƲ Ex-d-ia instrument 16 … 32 V DCOperating voltage UB - illuminated display and adjustment moduleƲ Non-Ex instrument 13.5 … 32 V DCƲ Ex-ia instrument - Power supplyFISCO model13.5 … 17.5 V DCƲ Ex-ia instrument - Power supplyENTITY model13.5 … 24 V DCƲ Ex-d-ia instrument No lighting possible (integrated ia barrier)Number of sensors per DP/PA segment coupler, max.Ʋ Non-Ex 32