WAGO-I/O-SYSTEM 750 Commissioning 49750-652 Serial Interface RS-232 / RS-485Manual1.2.0Configuration Sets the process image size.Help Opens the WAGO-I/O-CHECK online help.Pos : 82.3 /Serie 759 (WAGO-Softwar e)/WAGO-I/O-CHEC K/750- 0652 Seriell e Schnittstelle R S-232/RS- 485_Datenaus tausc hSeriell e Schnittstelle R S-232/RS- 485 750- 0652 (PA-Grösse) @ 14\mod_1361196391363_21.doc x @ 112211 @ 3 @ 18.1.3 Process Image SizeTo make settings on the "PI Mapping" (process image mapping) page, the processimage size of the master must be set first.Use the [Configuration] button on the toolbar to open the dialog for entering theprocess image size.Figure 19: Process image sizeChanges to the process image size!Note that with changes to the process data length, the structure of the processimage changes, and if necessary, changes to the configuration of the superiorcontroller may be necessary.The following selection box is displayed:Table 23: PI sizeSelection box SettingsProcess image size 8 bytes, 24 bytes*, 48 bytes*) Default settingWith the [Apply] button, you transfer the changed parameters to the non-volatilememory of the I/O module. A software reset is conducted so that the changes takeeffect. The dialog remains open.With the [Default] button, you select the default setting for this I/O module. Withthe [Apply] button, you then transfer the parameters to the non-volatile memoryof the I/O module.With the [Close] button, you close the configuration dialog without transferringany changed parameters to the non-volatile memory of the I/O module.