WAGO-I/O-SYSTEM 750 Connect Devices 27750-512 2DO 230V AC 2.0A/ Relay 2NOManualVersion 1.2.0Pos : 62 /All e Seri en ( Allgemei ne Module)/Ü bers chriften für alle Serien/Ansc hließ en/Geräte ansc hließ en - Ü bersc hrift 1 @ 3\mod_1234172889468_21.doc @ 27460 @ 1 @ 15 Connect DevicesPos : 63 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Lei ter an C AGE C LAM P ansc hließen - Ü bers chrift 2 und T ext @ 3\mod_1225448660171_21.doc @ 24928 @ 2 @ 15.1 Connecting a Conductor to the CAGE CLAMP ®The WAGO CAGE CLAMP ® connection is appropriate for solid, stranded andfinely stranded conductors.Only connect one conductor to each CAGE CLAMP® connection!Only one conductor may be connected to each CAGE CLAMP ® connection.Do not connect more than one conductor at one single connection!If more than one conductor must be routed to one connection, these must beconnected in an up-circuit wiring assembly, for example using WAGO feed-through terminals.Exception:If it is unavoidable to jointly connect 2 conductors, then you must use a ferrule tojoin the wires together. The following ferrules can be used:Length 8 mmNominal cross section max. 1 mm 2 for 2 conductors with 0.5 mm 2 eachWAGO Product 216-103 or products with comparable properties.1. To open the CAGE CLAMP ® insert the actuating tool into the openingabove the connection.2. Insert the conductor into the corresponding connection opening.3. To close the CAGE CLAMP ® simply remove the tool - the conductor isthen clamped firmly in place.Figure 10: Connecting a conductor to a CAGE CLAMP ®Pos : 64 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1