890362_b•en•21.03.2011We reserve the right to carry out improvements48WAREMA Quatronic dialog®Operating instructions7.3.4 Outside settings up/down,inside settings up/downThe effects of the settings are addressed below in more detail.A temperature control command can have a variety of effects, which you canselect in the Temp menu.Limit values:Normally, the DOWN limit value (Out or In) must be larger than the UPlimit value (Out or In): If the temperature reading exceeds the DOWN limitvalue, the DOWN move command is triggered or the sun control is switchedon.If the temperature reading drops below the UP limit value, an UP move com-mand is triggered or the sun control is switched off and an UP move com-mand is triggered.NOTE The temperature control has no delays since temperatures change slowly.7.3.5 InOM, OutOM, AllocsettingsOperating modes:If the inside/outside temperature control is to execute a move command, se-lect the Move setting in the InOM, OutOM menus.If the inside/outside temperature control is to enable the sun control, selectthe Sun setting in the InOM, OutOM menus.Allocation:One outside temperature sensor and/or up to 4 inside temperature sensorscan be connected to the Quatronic dialog. These sensors are allocated tothe 4 facades in the Alloc menu.omfort functionsTemperature control