245.6 WM1 and WM2 MenusThe Water Meter 1 and 2 menus are used to set up the type of meter and how to convert the water metersignal into volume. The Water Meter menus will be indicated on the display as follows:WM1 100 Gal or LitersReset Total This allows you to restart the totalizer display. Press the Up or Down arrow key to change the N to Y andpress ENTER to reset the totalizer to 0 gal. The totalizer will count up to a maximum of 99,999,999.After that it will reset itself to zero.Vol/contOnly appears if the WMType mode is Watercontactor.This allows you to set the volume of makeup per contact from the water meter.K FactorOnly appears if the WMType mode is PaddlewheelEnter the number of pulses per unit volume that the paddlewheel sensor sends out. This value is usuallyprinted on the sensor’s flow cell or in its instructions.Tot Units This is used to set the units of measure for the totalizer. Press ENTER, then use the up and down arrowkeys to toggle between "Gallons" and "Liters." Press ENTER when the desired choice is displayed.WM Type Press ENTER and then use the Up or Down arrow keys to select between Water Contactor, Paddlewheel,or Not Used.Figure 12 WM1 and WM2 MenusWM1 1000GalReset Total N1000 S 68° FWM1 1000GalWM1 1000GalTot Units GalWM1 and WM2 MenusENTEREXITNEXTPREV.WM1 1000GalWM Type PWM Type PPaddlewheelENTEREXITWM Type CWater Contactor3Legend1 Menu choice appears if WM Type is Water ContactorMenu choice appears if WM Type is PaddlewheelThis is the only menu shown if WM Type is Not Used.WM1 1000GalKFactor 999.92Tot Units GalGallonsENTEREXITTot Units GalLitersWM Type NNot UsedWM1 1000GalGal/Cont. 101orWM1 1000GalLit/Cont. 1023