10 YASKAWA ELECTRIC TOEP C710616 33A YASKAWA AC Drive L1000A Quick Start Guide3 Electrical Installation3 Electrical InstallationThe figure below shows the main and control circuit wiring.Note: 1. The drive should be implemented in the system in a way so that a drive fault causes the safety chain to open. Always use terminalMA-MB-MC for this purpose.2. Even though no fault is present conditions where the drive can not start can occur, e.g. when the Digital Operator is left in theProgramming Mode. Use the “Drive Ready” output (default set to terminals M5-M6) to interlock operation in such situations.<1> Remove the jumper when installing a DC reactor. Models CIMR-LC2A0085 through 0180 and 4A0045 through 0150 come with a built-in DCreactor.<2> The drive provides a stop function in compliance with Stop Category 0 (EN60204-1) and “Safe Torque Off” (IEC61800-5-2). It has beendesigned to meet the requirements of the EN954-1/ISO13849-1, Category 3 and IEC61508, SIL2. Using this function the number of motorcontactors can be reduced to one. Refer to Safe Disable Input Function on page 41 for details.<3> Never short terminals SP and SN, as doing so will damage the drive.<4> Disconnect the wire jumper between H1 - HC and H2 - HC when utilizing the Safe Disable inputs.CN5-CCN5-BCN5-AOption card connectorsOff OnThree-phasepower supply200 to 240 Vac or380 to 480 Vac50/60 HzR/L1S/L2T/L3MainSwitch FuseEMCFilterP1P2C1C2Photo Coupler 1(During Frequency Output)Photo Coupler 2(not used)Digital output5 to 48 Vdc2 to 50 mA(default setting)+++++MU/T1V/T2W/TUVW3GroundTerminals -, +1, +2, B1, B2 arefor connecting options. Neverconnect power supply lines tothese terminalsDC reactor(option)U XThermal relay(option)++++++U XS1S2S3S4S5S6S7DMDMA1A20 VACRRSSIGH1H2HCDriveB112 B22 kΩS8SC0 VFMAMACE (G)<1>+24 V+VMAM1M2MBMCJumper Braking resistor(option)Up command / StopNominal SpeedInspection OperationIntermediate Speed 1Not UsedMulti-functiondigtial inputs(default setting)Sink / Source modeselection wire link(default: Sink)Shield ground terminalMulti-functionanalog inputsPower supply +10.5 Vdc, max. 20 mAAnalog Input 1 (Speed Bias)-10 to +10 Vdc (20 kΩ)Analog Input 2 (Not used)-10 to +10 Vdc (20 kΩ)−V Power supply, -10.5 Vdc, max. 20 mAMEMOBUS/Modbuscomm. RS485/422max. 115.2 kBpsTermination resistor(120 Ω, 1/2 W)DIPSwitch S2Fault relay output250 Vac, max. 1 A30 Vdc, max 1 A(min. 5 Vdc, 10 mA)Multi-function relay output (Brake Control)250 Vac, max. 1 A30 Vdc, max 1 A(min. 5 Vdc, 10 mA)Multi-function analog output 1(Output Speed)-10 to +10 Vdc (2mA)Multi-function analog output 2(Output Current)-10 to +10 Vdc (2mA)EDM (Safety Electronic Device Monitor)Main CircuitControl Circuitshielded linetwisted-pair shielded linemain circuit terminalcontrol circuit terminalR/L1S/L2T/L3MotorShieldedCableM3M4Multi-function relay output (Output Contactor Control)250 Vac, max. 1 A30 Vdc, max 1 A(min. 5 Vdc, 10 mA)M5M6Multi-function relay output (Drive Ready)250 Vac, max. 1 A30 Vdc, max 1 A(min. 5 Vdc, 10 mA)SPSNDIP Switch S2Term. Res. On/OffJumper S3H1, H2Sink/Source Sel.Terminal boardjumper and switchFM+AM<3>Down command / StopLeveling SpeedNot Used<2><4>Safe Disable inputsPDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor