28 YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual6 Related Parameters6 Related ParametersThe following parameters are used to set up the drive for operation with the option.Confirm proper setting of parameters in Table 9 before starting network communications.Table 9 Related ParametersNo.(Addr. Hex) Name Description Valuesb1-01(180)<1>Frequency ReferenceSelectionSelects the frequency reference input source0: Operator - Digital preset speed d1-01 to d1-171: Terminals - Analog input terminal A1 or A22: MEMOBUS/Modbus communications3: Option PCB4: Pulse Input (Terminal RP)Default: 1Range: 0 to 4(Set to 3 forCompoNet only)b1-02(181)<1>Run CommandSelectionSelects the run command input source0: Digital Operator - RUN and STOP keys1: Digital input terminals S2: MEMOBUS/Modbus communications3: Option PCBDefault: 1Range: 0 to 3(Set to 3 forCompoNet only)F6-01(3A2)Operation SelectionafterCommunicationsErrorDetermines drive response when a bUS error is detectedduring communications with the option0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only <2>Default: 1Range: 0 to 3F6-02(3A3)External FaultDetection Conditions(EF0)Sets the condition for external fault detection (EF0)0: Always detected1: Detected only during operationDefault: 0Range: 0, 1F6-03(3A4)Stopping Method forExternal Fault fromCommunicationOptionDetermines drive response for external fault input (EF0)detection during CompoNet communication0: Ramp to Stop1: Coast to Stop2: Fast-Stop3: Alarm Only <2>Default: 1Range: 0 to 3F6-07(3A8)NetRef/ComRefSelection Function0: Multi-step speed reference disabled1: Multi-step speed reference allowedDefault: 1Range: 0, 1F6-08(36A)ResetCommunicationRelated ParametersDetermines which F6- and F7- parameters arereset to default values when the drive is initialized usingA1-03.0: Do not reset parameters1: Reset parametersDefault: 0Range: 0, 1F6-40(3D5)<3>MAC ID Selects the drive MAC addressNote: Used in the CompoNet Link ObjectDefault: 0Min: 0Max: 63